Product Overview
Advanced intelligence. Compact footprint. The S811+/S801+ line of intelligent technologies soft starters is designed to be the smallest, most compact soft starter in the market today. With this small size, it can easily fit in place of existing soft starter designs, wye-delta starters or across-the-line NEMA and IEC starters. This feature allows easy retrofits of existing motor control centers or enclosures and saves the expense of replacing existing structures or adding a new one to house a soft starter. The product is designed to work with 3-phase motors in a Delta (3-lead) configuration. The S811/S811+ works with all motors from fractional horsepower up to motors requiring 1000 amps of steady state current. The built-in over-load (in ranges from 12 - 1000 amps) and run bypass contactor make installation and setup quick and easy. The overload also offers some advanced protective functions to give additional motor protection. With the pump control option, it is the number one soft starter available for pumping applications. The unique soft stopping control provides a smooth transition for stopping a motor and eliminating the "water-hammer" effect that can damage pipes, valves and pumps.
- Attributes
- Documents
- Application
- Item Features
BrandEATON
Amperage Rating42/135 A
Coil Voltage24 VDC
Connection TypeIn-Line
Control TypePump
Country of OriginDO
Dimensions13 in L x 9-1/2 in W x 10 in H
Enclosure TypeOpen
Frequency Rating50/60 Hz
Manufacturer NameEaton
Number of Poles3
Operating Temperature-22 to 122 deg F
Phase3, 3 ph
SeriesS811
Starting ModesCurrent Limit/Kick/Ramp
Timing0.5 to 180 s
TypeNon-Combination Standard
Voltage Rating600 VAC
Wattage40/63/80 kW
Electrical Assemblies, Panels and EOEMs Applications
- 30 s ramp or 450% current limit at 50 deg C, inside the delta connection, pump control and extended ramp functions
- 40 kW at 230 VAC, 63 kW at 380 to 400 VAC, 80 kW at 440 VAC motor power
- http://videos.eaton.com/detail/video/3753115692001/soft-starter-ds7-up-to-32-a?autoStart=true&q=DS7