ELASTIMOLD 273ESA-18SURGE ELBOW ARR
Product Overview
Elastimold® Metal Oxide Varistor (MOV) surge arresters are fully shielded, fully submersible and are equipped with IEEE 386 interfaces for convenient energized connection with other 200 A loadbreak components. Units are compact, allowing installation in existing cabinetry. For application ease, arresters are available in 3 styles, elbow (ESA), parking Stand (PSA) and bushing (BSA). The PSA and BSA arresters permit direct connection eliminating the need for additional accessories. Elastimold® arresters provide high voltage lightning and switching surge protection of transformers, cable, equipment and other components typically located on underground power distribution systems. Proper placement, voltage selection and coordination with riser pole arresters minimizes damaging surge voltages by improving protective margins.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandElastimold®
Amperage Rating200 A
Country of OriginUS
Dimensions9.36 in L x 7.42 in W
Duty Cycle Voltage18 kV
Manufacturer NameABB
MaterialEPDM Rubber
Maximum Discharge Voltage80.5 kV
Operating Voltage25 kV
Series273ESA
Surge Protection Voltage15.3 kV RMS MCOV
Temperature Rating-40 to 65 deg C
TypeInsulated Shielded
Other
For providing high voltage lightning and switching surge protection of transformers, cable, equipment and other components typically located on underground power distribution systems and underground medium voltage applications
- EPDM rubber construction - Fully shielded and fully submersible for a variety of applications
- Compact size enables installation in your existing cabinetry, saving you money
- 4 AWG ground lead tethered to the jacket withstands 10000 A for 10 cycles without fusing
- Ground lead also controls end plug when ejected, preventing uncontrolled trajectory and maintains the housing shield ground connection after failure
- 56.5 kV at 1.5 kA/60 kV at 3 kA/64 kV at 5 kA/71 kV at 10 kA/80.5 kV at 20 kA maximum discharge voltage
- IEEE 386 interfaces provide convenient energized connection with other 200 A load break or dead break components
- Equipped with a fully rated 200 A switching and fault close load break bushing
ANSI Specified|IEEE 386|IEEE C62.11-2012