LITTELFUSE PGR-3100 GROU ND FAULT INDICATION SYSTEM W/ LEDS
LITTELFUSE PGR-3100 GROU ND FAULT INDICATION SYSTEM W/ LEDS
Stanion #PGR3100LIT
MFG #PGR-3100
UPC #79458177312
Product Overview
The PGR-3100 indicates the presence of voltage on each phase of a 3-ph system. The LEDs on the panel illuminate when voltage is present. When A ground fault occurs, the voltage on the faulted phase reduces to ground potential, causing the LEDs for the faulted phase to dim. On A resistance grounded or ungrounded system the LEDs for the unfaulted phases become brighter. Ungrounded ac systems are required by the national electrical code (NEC®) Article 250.21(B) and the Canadian electrical code part 1, section 10-106 (2) to have ground detectors, such as the PGR-3100, installed on the system. External potential transformers (PTs) can be used to step down system voltage, allowing the PGR-3100 to be applied to a ny system voltage. PTs are not required for system voltages upto 600 VAC.
- Attributes
- Documents
- Item Features
- Standards
BrandLittelfuse®
Country of OriginMX
Dimensions4.3 in W x 2.1 in D x 3.5 in H
Manufacturer NameLittelfuse
Mounting TypePanel
SeriesPGR-3100
Voltage Rating600 VAC
- Indicates presence of a ground fault and the faulted phase as well as phase to ground voltage on an energized bus
- Redundant long life LEDs (two per phase) to ensure reliability
- Lamp test button verifies LEDs are operating
- <30 VAC line to ground indicator off voltage
CSA File No. LR53428|UL Listed|NEC Article 250.21(B)|CEC Part 1 Section 10-106 (2)