MERSEN MPDB67560 PWR DIS DIS BLK AL INT 175A AD 6
MERSEN MPDB67560 PWR DIS DIS BLK AL INT 175A AD 6
Stanion #MPDB67560MER
MFG #MPDB67560
UPC #782001449452
Product Overview
The next generation power distribution block (PDB). Mersen power distribution blocks provide a safe and easy method of splicing cables, splitting primary power into secondary circuits and fulfilling requirements for fixed junction tap-off points. Unless noted otherwise, all blocks are UL and CSA approved while meeting spacing requirements for feeder and branch circuits in conjunction with UL 508 A and the national electric code. PDB options include single or dual conductor primary inputs and up to 30 secondary outputs. Specialty blocks are available allowing for up to 7 primary inputs.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandMersen
Amperage Rating175 A
ColorBlack
Country of OriginMX
Dimensions1.72 in W x 5 in D x 3.25 in H
Manufacturer NameMERSEN
MaterialPolycarbonate
Primary Connections/Pole1
Secondary Connection/Pole6
SeriesMPDB
Short Circuit Current Rating100 kA
TypeAdder Intermediate Open Style
Voltage Rating600 VAC
Wire Size14 to 2/0 AWG
Other
Cable Splicing, Splitting Primary Power into Secondary Circuits, Fixed Junction and Tap-Off Point Applications
- Aluminum connectors accept both aluminum or copper wire while copper connectors accept copper wire only and all 1-piece tin plated
- Connectors are all 1-piece tin-plated
- Insulators are virtually unbreakable, made of glass-filled polycarbonate
- See-through, hinged safety covers provide a greater degree of safety and shock resistance where required
- Hinged covers can be installed without tools
- 1 in through air and 2 in over surface between uninsulated live parts of opposite polarity meets requirements for feeder and branch circuit applications of UL508A
- Polycarbonate safety covers provide dead-front protection
- One cover is needed for each pole
- Each cover has a test probe hole in the center for circuit checking
- Adder poles for increased flexibility and ease-of-use
- Adder poles can be stacked to form multi-pole units in the field without the use of tools
- Adder poles allow for customization of primary and secondary wire combinations
- Part numbers are rated to accept DLO-type fine-strand wire, allowing users to connect flexible conductors
- 14 to 2/0 AWG 14 to 1/0 AWG (DLO) Al line, 14 to 2 AWG 14 to 3 AWG (DLO) Al load
RoHS Compliant|UL File No. E352417|CSA Class 6228-01, File No. 069363_0_000|CE Marked|UL94-V0 Flammability