O-Z/Gedney
OZ-G EYAM150 1-1/2-IN HOR/VERT SEALING FTG
O-Z/Gedney
OZ-G EYAM150 1-1/2-IN HOR/VERT SEALING FTG
Stanion #EYAM150OZ
MFG #EYAM-150
UPC #783126139044
Product Overview
O-Z/Gedney Conduit Sealing Fitting, Type EYAM Dust-Ignitionproof Explosionproof Raintight Horizontal Vertical, 1-1/2 in Size, For Use With: IMC/Rigid Metal Conduit, Malleable Iron, Electroplated Zinc, 2 in Dia x 6-3/4 in L Dimensions,
- Attributes
- Documents
- Includes
- Item Features
- Standards
- Warranty
BrandO-Z/Gedney
Country of OriginMX
Dimensions2 in Dia x 6-3/4 in L
FinishElectroplated Zinc
Manufacturer NameEmerson Electric
MaterialMalleable Iron
Size1-1/2 in
Suitable For Use WithIMC/Rigid Metal Conduit
TypeType EYAM Dust-Ignitionproof Explosionproof Raintight Horizontal Vertical
Removable Close Nipple
- To seal conduits in vertical or horizontal runs
- To minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduit
- 25% conductor fill
- Use with type EYC sealing compound and type EYF fiber
- Prevent passage of gases, vapors or flames from one portion of conduit system to another
- Restrict any explosion to the sealed off enclosure
- Prevent pressure piling within conduit system
- Required in class I, division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in class I, division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in class I, division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in class I, division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
- Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, division 2 locations
- Smooth, rounded integral bushing in each hub to protect conductor insulation
- Accurately tapped, tapered threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- Large opening for damming and filling
UL File No. E34997|CSA 009795|Class I Division 1/2 Group C/D, Class I Zone 1/2 Group IIA and IIB, Class II Division 1/2 Group E/F/G, Class III|UL 886|CSA C22.2|Number 30 NEC Article 500-503 & 505|Mil-F-28675
Limited