EDWARDS FX-5R FACP 5 ZONE 120V RED
Product Overview
Kidde® brand conventional fire alarm systems consist of 5 and 10 zone fire alarm control panels (FACP), an optional integrated upload/download DACT (dialer), intelligent/analog type detector features, serial annunciator modules and serial remote relay modules. All FACPs and components are listed to the 9th edition of the ANSI/UL 864 standard and CSFM/FDNY approved. These systems incorporate features designed to simplify installation, operation and maintenance, including front panel programming, one person walk testing and selectable IDC and NAC types. In addition, when used with CleanMe® compatible smoke detectors, these control panels provide intelligent type features such as remote maintenance alert and automatic drift compensation that significantly reduce the chance of a false alarm and simplify maintenance calls. Kidde® systems are powerful enough to meet the demands of todays life safety installations while leaving plenty of room to grow in the future. They support class A operation by combining pairs of on board IDCs or NACs to provide the necessary class A circuits.
- Attributes
- Documents
- Application
- Includes
- Item Features
- Standards
BrandEdwards Signaling™
Circuit Input5
Circuit Output2
ColorRed
Country of OriginCN
Dimensions19-1/2 in H x 14-1/4 in W x 3-3/4 in D
Display TypeLCD
Manufacturer NameUnited Technologies
MaterialSteel
Power SourceBattery
SeriesFX Series
Specifications120 VAC Input, 24 VDC Output, 3.5 A Current Capacity/Panel, 2 A Current Capacity/Circuit
Specifications MetCSFM Approved
Temperature Rating32 to 120 deg F
Type5-Zone Conventional
Other
To provide smoke and fire detection, occupant notification and off-premises signaling for small to medium sized buildings
Integrated DACT/Dialer, Serial Annunciator Module, F-XTR120 Expander Transformer and Serial Remote Relay Module
- CleanMe® feature provides remote annunciation of a dirty detector
- Automatic drift compensation with select detectors reduces false alarms and extends dust life
- Models with fully integrated upload/download DACT enables PC programming
- Zone or NAC pairs convertible to single Class A circuits
- Combination waterflow and supervisory IDCs
- NACs programmable by zone and individually selectable for notification appliances, continuous, temporal outputs or coded
- Front panel programmable simplifies installation and servicing
- Precision synchronization with compatible notification appliances and optional audible silence over two wires
- On-board relays for alarm, supervisory and trouble
- One person walk-test (audible or silent)
UL 864|ANSI Specified|ULC File No. S527|FDNY COA 6230|State Fire Marshal