EATON
C-H 15BHLE-200E FUSE HLE BOLT-ON 15KV 200E
Factory Availability
EATON
C-H 15BHLE-200E FUSE HLE BOLT-ON 15KV 200E
Factory Availability
Stanion #15BHLE200ECH
MFG #15BHLE-200E
UPC #7.82116E+11
Product Overview
Current limiting E-Rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating. They are physically dimensioned for easy installation in existing hardware to provide positive interruption even on low fault currents. E-Rated fuse constructions are available in ferrule, bolt-on and clip-lock and specialty mount fuses for AMPGARD® motor starters Outdoor rating available on select catalog numbers and open fuse indicator speeds troubleshooting by providing a positive visual indication of fuse operation.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandEATON
Amperage Rating200 A
Body Size18.9 in L x 3 in W x 3 in H
ClassE
Country of OriginDO
Frequency Rating50/60 Hz
Interrupt Rating63 kA
Manufacturer NameEaton
Mounting TypeBolted-On
Response Time600 s
TypeE-Rated Medium Voltage 2-Barrel
Voltage Rating15.5 kV
For use in medium voltage feeder circuit protection, medium voltage metal-enclosed switchgear, medium voltage transformer primary protection, medium voltage switches and indoor/outdoor applications
- Current limiting e-rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same e-rating
- E-rated fuses must have a defined current response time specified by ANSI C37.46
- E-rated fuses greater than 100 A must melt in 600 s at an RMS current within the range of 220 to 264% of the fuse's nameplate current rating
- E-rated fuses are physically dimensioned for easy installation in existing hardware
- Current limiting fuses provide positive interruption even on low fault currents
- The fuse limits the magnitude of electro mechanical stresses in the protected apparatus
- Open fuse indicator speeds trouble shooting by providing a positive visual indication of fuse operation
ANSI C37.46|BAA Compliant|IEEE C37.41