SQD 8536SAO12V02H308S STARTER 600VAC 9AMP NEMA
SQD 8536SAO12V02H308S STARTER 600VAC 9AMP NEMA
Stanion #8536SAO12V02H308SSQD
MFG #8536SAO12V02H308S
UPC #785901094104
Prop 65
Product Overview
Class 8536 Type S magnetic starters are used to switch electric motors and provide overload protection. They are available as open or enclosed products.
- Attributes
- Documents
- Application
- Includes
- Item Features
- Standards
- Warranty
BrandSquare D™
Amperage Rating9 A
Coil Voltage110/120 VAC
Connection TypeScrew Clamp
Country of OriginUS
Dimensions3.23 in W x 4.21 in D x 6.77 in H
Enclosure TypeNEMA 00/Open
Frequency Rating50/60 Hz
Manufacturer NameSchneider Electric
Motor Power1.5 hp at 200/230 VAC/2 hp at 460/575 VAC
Number of Poles3
Operating Temperature0 to 40 deg C
Overload RelayMotor Logic™ Solid State
Phase3 ph
Reset TypeMotor Logic™ Solid State
Series8536
Starting ModesMagnetic
TypeType S
Voltage Rating600 VAC
Wattage1.1 kW at 200/230 VAC/1.5 kW at 460/575 VAC
Construction, Infrastructure, Industrial Markets, Commercial Office Buildings And Building Automation, Used For Starting and Stopping Of AC Squirrel Cage Motors
Separate Control Circuit
- Flexible with four overload relays, Motor Logic solid state, TeSysT communication solid state, Adapted Bimetal and melting alloy types
- Customizable with hundreds of combinations of contactors, starters, combination starters, pump panels, two-speed starters, reduced- voltage starters, enclosure options and accessories
- Serviceable by replacing contacts and coils rather than replacing the entire product
- Simply service the part that is worn out
- https://www.youtube.com/embed/Gy1KrKzer3o
CE Certified|IEC 947-4-1|CSA 60905 Class 3211-04|ECCN EAR99|UL File E78351 NLDX|PROP65: This product can expose you to chemicals including: Lead and Lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov
18 Months