CRS-H EBMBD FD EBM DISCO NNECT SWITC
Factory Availability
CRS-H EBMBD FD EBM DISCO NNECT SWITC
Factory Availability
Stanion #EBMBDFDCRO
MFG #EBMBD FD
UPC #782274458236
Product Overview
Crouse-Hinds series EBM disconnect switches are used to disconnect motor, lighting and other circuits in locations made hazardous by the presence of flammable gases or vapors or ignitable dusts. They also provide disconnect means and short circuit protection (fusible version).
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandEATON
Country of OriginUS
Depth10-1/4 in
Electrical Ratings100 A
Height29.4 in
Manufacturer NameEaton
MaterialCopper-Free Aluminum
NEMA RatingNEMA 3/3R/4/4X/7B/7C/7D/9E/9F/9G/12
TypeDust-Ignitionproof Explosionproof Watertight
Width14.46 in
For used to disconnect motor, lighting and other circuits, in locations made hazardous by the presence of flammable gases or vapors or ignitable dusts, indoors or outdoors in damp, wet and dirty locations or in areas where frequent washdowns, heavy rain or water spray is prevalent, to provide disconnect means and short circuit protection (fusible version)
- Rugged corrosion-resistant cast copper-free aluminum construction
- Switch operating handle is located through the right side wall of the body, permits visual confirmation of correct alignment and operation
- Total compliance to the wiring end room requirements of the National Electrical CodeĀ®
- Semi-clamshell enclosure design, with an external flanged ground joint between body and cover makes interior components more accessible
- Minimum enclosure-to-enclosure spacing with little interference between the opened cover and an adjacent enclosure
- Stainless steel hinges allow the cover to swing well out of the way
- Stainless steel quick release captive hex head cover bolts
- Stainless steel springs provide clear indication cover bolts are fully retracted from body
- Neoprene cover gasket permanently attached to the cover seals out moisture
- Bodies have top and bottom drilled and tapped conduit entrances for power and conduits
- Removable reducers are supplied as standard, to accommodate smaller size conduits
- All conduit entrances are plugged
- Tap-on mounting feet
- Without switch
CSA C22.2 File No. 30|UL 1203