Product Overview
Each heater is identified by a catalog number stamped on one terminal. The heater application table indicates the range of full load motor current to which a given heater may be applied. Heaters should be selected on the basis of the actual full load current and service factor as shown on the motor nameplate or in the manufacturer's published literature. When motor and overload relay are in the same ambient and the service factor of the motor is 1.15 to 1.25, select heaters from the heater application table. If the service factor of the motor is 1 or there is no service factor shown or a maximum of 115% protection is desired, select one size smaller heater than indicated.
- Attributes
- Documents
- Application
- Item Features
- Standards
BrandEATON
Country of OriginDO
Enclosure TypeNEMA 0/1/2
Full Load Current1.96 to 2.15/2.27 to 2.48 A Ambient, 1.82 to 1.99/2.22 to 2.43 A Non-Comp
Manufacturer NameEaton
Trip TypeFast/Thermal
TypeType B100
For A200 series NEMA 0/1/2 starter, safety, emergency exit devices, industrial facilities and factories facility applications
- Select heater coils based on full load current (FLA) shown on motor nameplate
- Type A and b overload relay
- Heater coils are rated to protect 40 deg C rise and a service factor of 1.15
- 1.82 to 1.99 A, 2.22 to 2.43 A non-compensating full load current
CSA Certified|UL Listed